518565-01 - ACM

Case IH 518565-01 - ACM – ACM: Internal failure in EHR lever 7

Issue description

Indicates an internal failure in EHR lever 7 (which corresponds to EHR lever G). This fault code is logged against the Armrest Control Module (ACM).

Applies to these machines

  • MAGNUM AFS Connect
  • Case IH Magnum AFS Connect
  • Case IH Steiger AFS Connect
  • Case IH Puma AFS Series

Check the cause

  1. Check if the EHR lever was recently calibrated or if a controller/EHR control unit was changed without calibration

  2. Repeat the EHR lever calibration procedure to see if the module can successfully relearn the lever's position

  3. Download the correct level of software to the module and perform the calibration procedure once more

  4. Verify that the wiring harness and connectors between the EHR lever and the Armrest Control Module (ACM) are secure and undamaged

Repair steps

  1. Power down and depressurize

    Power down the tractor and ensure the hydraulic system is depressurized.

  2. Access EHR lever assembly

    Open the armrest controller housing to access the EHR lever assembly.

  3. Disconnect electrical connector

    Disconnect the electrical connector for the affected EHR lever (Lever 7 / G).

  4. Remove faulty lever

    Remove the faulty EHR lever from the armrest control panel.

  5. Install replacement lever

    Install the replacement EHR lever and reconnect the wiring harness.

  6. Reassemble housing

    Reassemble the armrest housing.

  7. Perform calibration

    Turn the tractor on and use the Electronic Service Tool (EST) or the tractor's Pro display to perform a mandatory EHR lever calibration procedure for the new lever.

Parts you might need

(3)
  • Electro-Hydraulic Remote (EHR) Lever (Black)

    47995201

    Replaced by / Alternate Part # 90493683

  • Set of Levers (EHR, 6 Remotes)

    84235842

    Replaced by Part # 90493669 (if applicable to the specific build)

  • Armrest ACM (Remanufactured ECU)

    91807743R

    If the internal failure is determined to be on the ACM board itself rather than the lever

Get help to fix this fault by requesting a quote