John Deere 002172.09 – CCU or ECU/VCU: CAN BUS Message Fault SCV 12, Front Chassis Module (SCO)
Issue description
A communication error has occurred on the CAN bus, indicating that the main vehicle control unit has lost connection with the Secondary Hydraulic Control Unit (SCO) at source address 172. The SCO, also known as the Front Chassis Module, manages the Selective Control Valves (SCVs). When this fault is active, messages from the SCO are not received, resulting in a loss of function for the affected SCV circuits.
Applies to these machines
16 machines- 6145R
- 6155R
- 6175R
- 6195R
- 6215R
- 8120
- 8220
- 8320
- 8420
- 8520
- 9230
- 9330
- 9420
- 9430
- 9530
- 9630
Check the cause
Check for other active or stored fault codes that may indicate a broader CAN bus or power supply issue.
Perform a cold boot by turning the key switch OFF for at least 60 seconds, then restart the machine to see if the communication fault clears.
Perform a CAN bus resistance check at the 9-pin diagnostic connector (Pins C and D) with the battery disconnected. The expected reading is approximately 60 Ohms.
Perform a CAN bus voltage check with the key ON and engine OFF. Pin C (CAN High) should be 2.5V to 3.5V, and Pin D (CAN Low) should be 1.5V to 2.5V.
Visually inspect the wiring harness leading to the SCV stack and the Front Chassis Module (SCO) for chafing, pinching, or corrosion.
Inspect the SCO module connectors for corrosion, pushed-out pins, or loose connections.
Repair steps
Isolate the fault
If the initial CAN bus resistance check shows 120 Ohms, unplug controllers one by one until the resistance returns to 60 Ohms to isolate the open circuit.
Disconnect SCO module
Locate the Secondary Hydraulic Control Unit (SCO) on the tractor frame and disconnect its main electrical connector.
Re-check CAN resistance
With the SCO module disconnected, repeat the resistance measurement at the diagnostic port. If it reads 120 Ohms, the SCO module or its internal resistor is faulty. If it remains unchanged, the fault is in the main CAN harness.
Inspect and test harness
Inspect the pins on the SCO controller and harness connector for damage. Test for continuity on the CAN High and CAN Low wires between the SCO connector and the diagnostic port to rule out a wire break.
Replace SCO controller
If diagnostic tests point to an internal failure of the SCO module and the wiring is confirmed good, replace the controller.
Program and calibrate
Have an authorized dealer program the new controller using Service ADVISOR software and perform an SCV calibration procedure.
Parts you might need
(5)SCV Controller
RE201259For 8000/9000/9020 Series Tractors, often listed for models like the 8420, 9420, and others.
- Rear Electronic Control UnitAL232351
For 6R Series Tractors, including the 6155R.
- Electronic Control UnitAL220155
Fits various 6R models
- Short Cut Bar ControllerRE569887
Used on models like the 6155R
Verify fitment with serial number
Get help to fix this fault by requesting a quote