Technical info
Approval certificates VDE Reg N° 7690 Application In dry and moist rooms for light and medium mechanical stresses. Outdoors only protected. Not in Water. As supply or interconnecting cable for measuring, controlling and regulating, according to DIN VDE 0113 for computer units for control equipments on machine tools, assembly lines. For control equipment on conveyors and production lines for controlling, regulating, and monitoring work processes, industrial plants and production lines when temporatily freely moved and no periodic recurrence without forced guidance. Design Conductor Copper bare stranded, VDE 0295 Class 5 Insulation PVC Type YI 2 (Polyvinyl chloride) Screen Al coated tape, tinned copper braid Outer sheath PVC Type YM 2 (Polyvinyl chloride), colour grey Core identification according to DIN VDE 0293:1990-01 JZ/OZ: black, white printed numbers and with/or without green/yellow core. JB: cloured cores according to HD 308 S2
Conductor category
Class 5 = flexible
Core cross section
0,5 mm²
Core identification
Numbers
Content in sale unit
1 pcs
Screen over stranding
Braiding
Outer diameter approx.
13,7 mm
Manufacturer Product ID
16335
Core identification type
Numbers
Material core insulation
PVC
Core insultation material
PVC
Conductor category class code
5
Screen over stranding element
None
Type of screen over stranding
Braiding
Nominal cross section conductor
0,5 mm²
Low smoke according to EN 61034-2
No
Working ambient temperature range
-10-80
Assembling ambient temperature range
-40-80 °C
Halogen free according to EN 50267-2-2
No
Oil resistant according to EN IEC 60811-404
No
Flame retardant according to IEC/EN 60332-1-2
Yes
Fire reaction class code according to EN 13501-6
Eca
Reaction-to-fire according to EN 13501-6: Acidity
None
Reaction-to-fire according to EN 13501-6: Smoke production
None
Low temperature resistant according to EN 60811-504+505+506
No
Permitted cable outer temperature during assembling/handling
-10.0-80.0 °C
Min. permitted bending radius, moving application/free movement
137 mm
Permitted cable outer temperature after assembling without vibration
-40.0-80.0
Reaction-to-fire according to EN 13501-6: Flaming droplets/particles
None
Min. permitted bending radius, stationary application/permanent installation
69 mm